Opportunity

SAM #N4523A26Q5734

Lease and support of a 500 kW emergency diesel generator for Puget Sound Naval Shipyard

Buyer

Puget Sound Naval Shipyard

Posted

October 02, 2026

Respond By

October 07, 2026

Identifier

N4523A26Q5734

NAICS

532490, 532412

Puget Sound Naval Shipyard and Intermediate Maintenance Facility needs a rental emergency diesel generator to support the submarine Jimmy Carter in Bremerton, Washington. - Government buyer: Department of the Navy, U.S. Navy — Puget Sound Naval Shipyard and Intermediate Maintenance Facility (PSNS & IMF). - Procurement: Lease one 500 kW emergency diesel generator (EDG). No OEM, manufacturer, or vendor is named in the provided materials. - Generator requirements: 460 VAC, three-phase, 60 Hz; brake horsepower below 2,000; emissions certification; and specified electrical protection, controls, alarms, and automatic shutdown. - The unit must have a double-wall UL 142 fuel tank sized for 16 hours at full load, safely refuelable while operating, and an outdoor-rated NEMA 3R ISO enclosure with crane lift points and secondary fluid containment. - Before delivery, the contractor must perform specified maintenance and successfully load-test the generator at 80% or more of capacity for one hour. - Contractor support: Coordinate delivery and pickup; provide a 15-minute delivery test, one hour of on-site training, an operation and maintenance manual, EPA off-road engine certification, and 24/7 technical support. - For an equipment issue, the contractor must determine within four hours whether repair or replacement is needed and restore operation within 48 hours; a half-hour retest is required after repair or replacement. - Rental structure: Two-month base period with an 11-month option, for up to 13 months total. Expected generator use is less than 50 hours per calendar year.

Description

Puget Sound Naval Shipyard (PSNS) requires 1 ea. 500kW Emergency Diesel Generator (EDG) for use in

Bremerton, WA. The Contractor shall provide all management, labor, equipment, tools and parts as necessary

to provide and support, during the duration of the contract, one (1), self-contained diesel generator system

capable of supplying electrical power per the requirements set forth in the Performance Work Statement

(PWS). The rental of one (1) each 500kW diesel generator will serve as part of an emergency power supply

system for providing primary power and/or standby backup power. Expected run time for the leased diesel

generator is less than 50 hours in a calendar year. The diesel generator shall be capable of reliably supplying

electrical power with electrical ratings of 460VAC, 3-phase, 60 Hz and minimum kilowatt (kW) power ratings

of 500kW. All generators shall have a brake horsepower rating less than 2,000.