# SAM #N4523A26Q5734

Lease and support of a 500 kW emergency diesel generator for Puget Sound Naval Shipyard

**Buyer:** Puget Sound Naval Shipyard
**Posted:** October 02, 2026
**Respond By:** October 07, 2026
**Identifier:** N4523A26Q5734
**NAICS:** 532490, 532412

Puget Sound Naval Shipyard and Intermediate Maintenance Facility needs a rental emergency diesel generator to support the submarine Jimmy Carter in Bremerton, Washington.
- **Government buyer:** Department of the Navy, U.S. Navy — Puget Sound Naval Shipyard and Intermediate Maintenance Facility (PSNS & IMF).
- **Procurement:** Lease one **500 kW emergency diesel generator (EDG)**. No OEM, manufacturer, or vendor is named in the provided materials.
- **Generator requirements:** 460 VAC, three-phase, 60 Hz; brake horsepower below 2,000; emissions certification; and specified electrical protection, controls, alarms, and automatic shutdown.
  - The unit must have a double-wall UL 142 fuel tank sized for 16 hours at full load, safely refuelable while operating, and an outdoor-rated NEMA 3R ISO enclosure with crane lift points and secondary fluid containment.
  - Before delivery, the contractor must perform specified maintenance and successfully load-test the generator at 80% or more of capacity for one hour.
- **Contractor support:** Coordinate delivery and pickup; provide a 15-minute delivery test, one hour of on-site training, an operation and maintenance manual, EPA off-road engine certification, and 24/7 technical support.
  - For an equipment issue, the contractor must determine within four hours whether repair or replacement is needed and restore operation within 48 hours; a half-hour retest is required after repair or replacement.
- **Rental structure:** Two-month base period with an 11-month option, for up to 13 months total. Expected generator use is less than 50 hours per calendar year.

### Description

<p>Puget Sound Naval Shipyard (PSNS) requires 1 ea. 500kW Emergency Diesel Generator (EDG) for use in</p>

<p>Bremerton, WA. The Contractor shall provide all management, labor, equipment, tools and parts as necessary</p>

<p>to provide and support, during the duration of the contract, one (1), self-contained diesel generator system</p>

<p>capable of supplying electrical power per the requirements set forth in the Performance Work Statement</p>

<p>(PWS). The rental of one (1) each 500kW diesel generator will serve as part of an emergency power supply</p>

<p>system for providing primary power and/or standby backup power. Expected run time for the leased diesel</p>

<p>generator is less than 50 hours in a calendar year. The diesel generator shall be capable of reliably supplying</p>

<p>electrical power with electrical ratings of 460VAC, 3-phase, 60 Hz and minimum kilowatt (kW) power ratings</p>

<p>of 500kW. All generators shall have a brake horsepower rating less than 2,000.</p>