Opportunity

SAM #36C249-27-AP-1027

VA market research for Caterpillar generator switchgear testing and SEL-351A relay diagnostics

Buyer

Vanco 9

Posted

November 16, 2026

Respond By

November 26, 2026

Identifier

36C249-27-AP-1027

NAICS

541380

The Department of Veterans Affairs is seeking market information for testing the Caterpillar CHP generator switchgear at Alvin C. York VA Medical Center. - Government buyer: Department of Veterans Affairs, Network Contracting Office 9; Tennessee Valley Healthcare System; Alvin C. York VA Medical Center, Murfreesboro, Tennessee. - OEMs: Caterpillar (Combined Heat & Power generator) and SEL (SEL-351A protective relay). The attachment filename references Qualus, but the notice does not identify it as the selected or required service provider. - Requested equipment testing: 3 current transformers (CTs), 2 sets of potential transformers (PTs), and 1 SEL-351A relay (part number stated as SEL-351 A). - Requested services: Visual and mechanical inspection plus electrical testing of the CTs, PTs, and relay. CT testing includes insulation resistance, polarity, ratio, excitation, burden, and dielectric withstand tests. PT testing includes insulation resistance, polarity, turns ratio, burden, and dielectric withstand tests. Relay work includes event-log download and checks of analog inputs, protection elements, control functions, digital inputs, and output contacts or SCRs; specified records are to be reset or deleted after testing. - Additional work and deliverables: One technician for up to 8 hours to investigate a reverse kVAR trip, followed by a comprehensive findings report with recommendations. - Notable requirements: Contractor supplies transportation, labor, parts, materials, tools, and equipment. Work is planned for two site visits and should start as soon as possible after award. The work is warranted for one year after acceptance. - Opportunity status: Market research only; no pricing is requested and no award commitment is made.

Description

The Department of Veterans Affairs, Network Contracting Office 9, seeks capable sources for one-time diagnostic testing of APT generator switchgear at the Alvin C. York VA Medical Center in Murfreesboro, Tennessee.

The work includes testing three current transformers, two sets of potential transformers, and one SEL-351A protective relay; providing up to eight technician hours to investigate reverse kVAR trips; and submitting a written report with findings and recommendations.

Anticipated classification: NAICS 541380, Testing Laboratories and Services ($19 million size standard); PSC H261.

Interested firms should email shania.kimbrough@va.gov by November 24, 2026, at noon CT, using the subject APT Generator Switchgear Testing. Include your company name, UEI, point of contact, business size and applicable SBA certification, relevant testing experience, and availability. State whether you would quote if solicited, who would perform the field testing, and whether you need any special software or access to the existing relay.

This notice is for market research only. It is not a solicitation or a commitment to award. No pricing is requested.

View original listing