Opportunity
SAM #W912P526QA032
Supply and Delivery of DC and AC Preferred Systems for USACE Nashville District
Buyer
Nashville District, USACE
Posted
August 04, 2026
Respond By
August 10, 2026
Identifier
W912P526QA032
NAICS
335313, 335999, 335311
The U.S. Army Corps of Engineers, Nashville District (USACE-LRN), is seeking information from industry for the supply and delivery of DC and AC preferred system components for hydroelectric dam applications. - Government Buyer: - U.S. Army Corps of Engineers, Nashville District (USACE-LRN) - Department of Defense, US Army Corps of Engineers - OEMs and Vendors: - No specific OEMs or vendors are named in the notice - Products/Services Requested: - Two 10kVA static inverters - Four isolation breakers - One 10kVA bypass transformer - One 125VDC panelboard - One 120VAC preferred AC panelboard - One emergency lighting panel board - One preferred AC sub-panel with all breakers and ancillary equipment - One 450kW outdoor diesel generator AC load bank - One 480V manual transfer switch - New conduits and cables - One hydrogen sensor - One air flow switch - One differential pressure switch - One smoke detector - Three warning lights - One battery disconnect switch - One automatic transfer switch - One DC load bank plug - One battery breaker - Two battery charger breakers - One load bank breaker - One Level 4 Maximum Duty 3-hour fire-rated steel door and frame assembly with glass window - One 3-hour fire rated HVAC damper for a 10"x8" duct with hardware and spare fusible links - Sufficient ductwork materials for a new branch off an existing duct - One centrifugal exhaust fan with spark resistant motor and mounting equipment - One combination emergency wash station with eye wash and deluge shower capabilities - Unique or Notable Requirements: - Expedited delivery capability may be required - Experience with hydroelectric dam equipment is preferred - NAICS code: 335313 (Switchgear and Switchboard Apparatus Manufacturing) - No part numbers or purchase quantities specified
Description
Request for Information: The U.S. Army Corps of Engineers, Nashville District is issuing this Request for Information to determine a competitive basis for the procurement described. This is not a solicitation. No reimbursement will be made for any costs associated with providing information in response to this survey.
This survey is for market research purposes only. Only contractors capable of performing this type of work should respond to this Request for Information.
Requirement: This project is for the supply and delivery of components identified in this request. The contractor shall provide all personnel, equipment, supplies, facilities, transportation, tools, materials, supervision, and other items to perform the work herein.
a. Two 10kVA static inverters (IV1, IV2), four isolation breakers, and one 10kVA bypass transformer.
b. One 125VDC panelboard, one 120VAC preferred AC panelboard, one emergency lighting panel board and one preferred AC sub-panel including all breakers, ancillary equipment, and associated bus.
c. One 450kW outdoor diesel generator AC load bank and one 480V manual transfer switch.
d. New conduits and cables.
e. One hydrogen sensor, one air flow switch, one differential pressure switch, one smoke detector and three warning lights.
f. One battery disconnect switch, one automatic transfer switch, and DC load bank plug.
g. One battery breaker, two battery chargers breakers, and one load bank breaker.
h. Level 4 Maximum Duty 3-hour fire-rated steel door and frame assembly with a 3-hour fire-rated glass window.
i. One 3-hour fire rated HVAC damper for a 10"x8" duct and all the hardware necessary for it including 2 spare fusible links.
j. Sufficient ductwork materials for the addition of a new ductwork branch off of an existing 10"8" supply duct and running 50 feet, including 4 right angle turns.
k. One centrifugal exhaust fan with a spark resistant motor to exhaust a minimum of 285 CFM of air and mounting equipment to mount the fan to an exterior wall.
l. One combination emergency wash station with eye wash and deluge shower capabilities.
NAICS: The anticipated NAICS code for this requirement is 335313, Switchgear and Switchboard Apparatus Manufacturing, size standard of 1,250 employees.
Survey: Please send responses to the Market Survey to R. Brent Hester at Richard.B.Hester@usace.army.mil and Kenyanna Jennings at Kenyanna.L.Jennings@usace.army.mil
Name of Firm: CAGE: Point of Contact (include email address) Are you classified as a small business under the following NAICS codes? If so, do you fall into a sub-category (e.g. HubZone, 8(a), SDVOSB, WOSB, etc.)? 335313, Switchgear and Switchboard Apparatus Manufacturing – 1,250 employees. If this requirement is advertised, do you anticipate submitting a quote? Can your company provide expedited delivery of equipment? Does your company manufacture these components? Has your company completed work for USACE? Has your company supplied equipment to hydroelectric dams? Please provide any additional information you feel is necessary.