Opportunity

SAM #N6274226RSEL387L

Sources Sought for SEL-387L Transformer Protection Relay

Buyer

NAVFAC Pacific

Posted

July 17, 2026

Respond By

July 31, 2026

Identifier

N6274226RSEL387L

NAICS

335314, 335313, 335999

NAVFAC Pacific, under the Department of Defense and Department of the Navy, is seeking sources for a transformer protection relay for Pearl Harbor Naval Shipyard and IMF Joint Base Pearl Harbor-Hickam, Hawaii. - Government Buyer: - Naval Facilities Engineering Systems Command, Pacific (NAVFAC Pacific) - Department of Defense, Department of the Navy - OEM Highlighted: - Schweitzer Engineering Laboratories (SEL) is specified as the OEM for the SEL-387L relay - Products/Services Requested: - Transformer protection relay with performance equal to SEL-387L - Must provide: - Line differential protection - Comprehensive backup protection - Line monitoring - Event reporting and monitoring - Panel control switches - Compatibility with existing system is required - Notable Requirements: - Respondents must submit detailed technical data to demonstrate product compatibility and equivalence to SEL-387L - Only products meeting all specified requirements will be considered - Incomplete or vague submissions may be disregarded - No other OEMs or vendors are mentioned in the notice

Description

Notice of intent to use a brand name product.  The Naval Facilities Engineering Systems Command, Pacific (NAVFAC Pacific) is performing a market survey to determine if other potential sources of supply can provide a transformer protection relay that has equal performance requirements as the SEL-387L, manufactured by Schweitzer Engineering Laboratories (SEL), 2350 NE Hopkins Court, Pullman, WA 99163.

Fiscal Year 2027 SIOP PROJECT P-8026 ELECTRICAL BACKBONE Pearl Harbor Naval Shipyard and IMF Joint Base Pearl Harbor-Hickam, Hawaii, requires transformer protection relay that has equal performance requirements as the SEL-387L with the following characteristics:

Line Differential Protection – Protect transmission or distribution lines using current differential protection for high-speed clearing of internal line faults. Provide dual-slope differential elements with external fault security and communications-assisted protection for internal fault detection while maintaining stability during external faults.

Backup Protection – Provide comprehensive backup protection including phase, negative-sequence, and ground overcurrent elements, directional overcurrent elements, breaker failure protection, and configurable distance or permissive tripping functions as required for reliable line protection.

Line Monitoring – Monitor three-phase currents, voltages (when applicable), frequency, power, sequence quantities, and communications-assisted protection status. Provide fault location and disturbance analysis capabilities to support system operation and maintenance.

Reporting and Monitoring – Provide event reporting with sequential event recorder (SER), oscillographic event reports, fault records, and communications diagnostics to document faults, trips, currents, voltages, and relay operations for post-event analysis.

Panel Control Switches – Conveniently sized operator controls shall be located on the relay front panel and configured to track associated operator control functions, including breaker control, relay status, and programmable pushbutton operations.

This notification is for market research purposes only to identify if other potential sources of supply can meet the requirements of the Government. This is not a request for proposals, quotes, or an invitation for bid. The intent of this notice is to identify other potential sources of this product. To be considered, please submit detailed technical data for the Government to conduct a comprehensive evaluation of your manufactured product to ensure compatibility with the existing system. In accordance with FAR 15.201(e), a response to this notice is not an offer and cannot be accepted by the Government to form a binding contract. The responder is solely responsible for the information it submits and any associated costs. The Government reserves the right to disregard any submittal that is incomplete or vague. Please do not submit company brochures. Please submit complete information via electronic mail to Ms. Annette Tijerina at annette.t.tijerina.civ@us.navy.mil no later than 30 July 2026 at 2:00 p.m. H.S.T.  Any information received after the due date/time will not be considered. Any information provided to the Government in response to this RFI will become U.S. Government property and will not be returned. All proprietary or classified information will be treated appropriately.

View original listing