237990, 237110, 238210

This procurement opportunity is for the redesign and installation of chemical waste lift stations at Robins Air Force Base, Georgia, managed by the U.S. Air Force 402 MXSG/MXDPM and Air Force Sustainment Center. - Government Buyer: - U.S. Air Force, 402 MXSG/MXDPM and Air Force Sustainment Center, Robins Air Force Base - Products/Services Requested: - Six (6) 56-Gallon Duplex Vertical Pump Lift Stations - Each station includes two electric pumps (CPVC or 316 Stainless Steel), polypropylene tank (50-75 gallons), stainless steel control panel (Nema 4x), 120V or 208V power supply, and automation features (disconnect switches, hands-off-auto, level sensors) - Designed for hazardous liquid chemical waste (acid and chrome waste) - Six (6) FLEX Conduit sets for installation - Six (6) upgraded Nema 4x stainless steel control panels - One (1) engineer on site for startup and training (one day for up to five government personnel) - Commercial drawings/models, environmental and energy management system documentation, safety plan, and accident/incident reporting - Unique/Notable Requirements: - All tools, parts, materials, equipment, labor, transportation, startup, and training must be provided by the contractor - Engineering drawings required within 4 weeks of order; equipment delivery within 12 weeks after drawing acceptance - 12-month warranty from equipment startup - System must comply with environmental and safety documentation requirements - No specific OEMs or part numbers are specified in the solicitation or attachments

Description

The Contractor shall provide all the tools, parts, materials, equipment, labor, transportation, startup, and training for a redesigned lift station to the Commodities Maintenance Group (CMXG) at Robins Air Force Base (AFB), Georgia. These lift stations will be used to transport liquid chemical waste that could present environmental danger (i.e. acid waste, chrome waste).

Each Lift Station shall have the following features: • Two (2) electric pumps made of CPVC or 316 Stainless Steel. Pump fittings must be CPVC with a two (2) inch maximum nominal size. The pump flowrate should be 25 gallons per minute per pump. The pump must have a 30-foot total dynamic head. • The tank material shall be polypropylene, with a volume of 50 to 75 gallons and a single tank containment style. • The dimensions of the lift station shall be four (4) feet long, three (3) feet wide, and four (4) feet high. • The control panel enclosure shall be made of stainless steel. • The power supply shall be 120V or 208V. • Each pump shall have disconnect switches, hands-off-auto, and level sensors for automation on/off pump operation.

View original listing