Opportunity
SAM #FA813726R0038
Tinker AFB Building 6002 Main Distribution and Branch Panel Board Replacement
Buyer
AFSC PZIOC
Posted
May 15, 2026
Respond By
June 01, 2026
Identifier
FA813726R0038
NAICS
238210, 238220, 238290
This opportunity seeks qualified contractors to repair and replace main distribution and branch panel boards at Tinker Air Force Base, Building 6002, Oklahoma. - Government Buyer: - U.S. Air Force, Air Force Materiel Command (AFMC), 72nd Air Base Wing Civil Engineering (72 ABW/CE), Air Force Sustainment Center (FA8137 AFSC PZIOC) - Products/Services Requested: - Demolition and replacement of main distribution and branch panel boards (including panelboards 6002-PNL-1 and 6002-PNL-2) - Installation of new electrical components: feeder cables, service entrance conductors, ground rods, wireway gutter, GFCI receptacles, LED strip lights, fire protection sprinklers, manual pull station, and combination audible-visual notification devices - Associated architectural, mechanical, and fire protection work - Project management, quality control, health and safety program management, construction scheduling, and progress reporting - Product Details: - Main Distribution Panelboard 6002-PNL-1: 800A MCB, 208Y/120V, 3-Phase, Nema 1 enclosure, copper bars, grounding bar, 20% spare breaker space - Branch Panelboard 6002-PNL-2: 225A MCB, 208Y/120V, 3-Phase, Nema 1 enclosure, copper bars, grounding bar, 20% spare breaker space - Integration with existing Honeywell Fire-Lite ES-200x fire alarm system - Notable Requirements: - Mandatory site visit for proposal eligibility - Contractor must complete Entry Authorization List (EAL) for base access and FOD awareness training - Compliance with UFC, Air Force, and OSHA/EM 385-1-1 standards - Coordination with utility companies and building managers - Detailed construction schedule and weekly progress reporting - Project duration: 370 calendar days after notice to proceed - No specific OEMs or part numbers are named; panelboards and components must meet specified technical and performance standards - Place of Performance: Tinker Air Force Base, Building 6002, Oklahoma
Description
This order proposal request is only available to current MACC-BOA holders.
The work to be performed under the terms of this Order consists of furnishing all materials, labor, plant, tools, transportation, equipment, testing services, quality control, and incidentals required to accomplish the repair/replacement of the main distribution & branch panel boards in building 6002 at Tinker Air Force Base (AFB), Oklahoma (reference the project drawings for additional location information). This is a construction-only order.
The Contractor shall perform a site investigation to verify existing conditions. If necessary, additional as-built drawings are available from 72 ABW/CE - Engineering Support, located in B400 on Tinker AFB.
The Contractor shall be responsible for identifying the necessary logistical, architectural, and structural work elements required to perform the work as described herein. Assemblies, framework, fixtures, or apparatus not readily identified on the project drawings, specifications, or the Statement of Work (SOW) shall be provided by the Contractor as required for a complete, fully operating, and functioning system or systems ready for use by the Government.
Information such as floor plan layouts and dimensions; structural, mechanical, and electrical data; and location of underground utilities provided by the Government for existing and new construction are based on available as-built documentation, field observation, and equipment selected as design basis by the Government. This information is to be considered approximate and shall be field verified by the Contractor.
This project will not require contractor personnel to perform work and/or operate vehicles on flight lines, runways, taxiways, parking ramps, or in aircraft hangers or maintenance areas. However, all contractor personnel are still required to receive FOD awareness training in accordance with Tinker Air Force Base Instruction (Tinker AFBI) 21-100.
IAW National Institute of Standards and Technology (NIST) Special Publication (SP) 800-171, the requirement does not include CUI residing on or transiting through contractor and/or subcontractor systems.
Site visit attendance is mandatory to be considered eligible for submission of proposal. RSVP email confirmation of intent to attend the site visit to the primary and secondary points of contact with Entry Authorization List (EAL) information by 11:59 PM CST, Friday, May 22nd, 2026. If a Contractor/Subcontractor fails to meet this deadline, the site visit information will not be released to your organization. Order documents not able to be uploaded to SAM.gov will be provided to contractors who RSVP'd their intent to attend the initial site visit.
Attachments include an EAL spreadsheet. Please fill-in all information for individuals who will need/do not currently have Base access. Please ensure all information requested in the EAL is filled out accurately and full names matching state-issued IDs are utilized to assure Security Forces can process the requests for Base Access in a timely manner. If an individual has Base access, their name is all the information needed. Please try to limit your parties to seven attendees per Contractor.
The site visit is scheduled for June 3rd, 2026 at 10:00 A.M at the project performance site. More specific meeting details will be shared with contractors who have sent an RSVP.
This notice also serves as the formal Synopsis for the requirement.