# SAM #36C25527R0020

Building 51 roof replacement at the St. Louis VA Medical Center, Jefferson Barracks

**Buyer:** VA Health Administration Network Contracting Office 15
**Posted:** November 23, 2026
**Respond By:** December 07, 2026
**Identifier:** 36C25527R0020
**NAICS:** 236220

The Department of Veterans Affairs is seeking a contractor to replace Building 51’s roofs at the St. Louis VA Medical Center, Jefferson Barracks.
- **Government buyer:** Department of Veterans Affairs, Network Contracting Office 15; contracting contact identified as Jennifer Hill.
- **Scope:** Firm-fixed-price construction for approximately 56,000 square feet of roofing, subject to field verification, including demolition and installation of mechanically fastened insulation, adhered cover board, and a fully adhered 70-mil TPO membrane with hot-air-welded seams.
- **Products and quantities:** Four skylights; two expansion-joint weatherproofing sections of approximately 40 linear feet each; approximately 600 linear feet of roof walking-pad routes; and one penthouse roof-access ladder.
- **Related work:** Flashing, drainage improvements, lightning-protection and warning-line work, correction of approximately 250 square feet of depressed roofing, and other associated roof repairs.
- **OEMs and vendors:** No roofing manufacturers, OEMs, or project vendors are named; proposed materials and systems are subject to VA review.
- **Notable requirements:** Keep the occupied, 24/7 building operational and watertight during construction; provide phasing and protections for occupants and HVAC intakes; submit required shop drawings and structural calculations; and complete testing, closeout, and as-built drawings. Includes a 20-year no-dollar-limit warranty.
- **Set-aside and estimated value:** Total set-aside for Service-Disabled Veteran-Owned Small Businesses; estimated project cost is $2 million to $5 million.
- **Performance duration:** Complete after Notice to Proceed. The documents state both 222 calendar days, including closeout, and an estimated 210 calendar days, so the duration is inconsistent.

### Description

Project # 657-27-103JB, FCA Replace Building 51 Roof

The Department of Veterans Affairs, Network Contracting Office (NCO) 15, has a requirement to Replace Building 51 Roof, project number 657-27-103JB, located at the U.S Department of Veterans Affairs, Str. Louis VAMC Jefferson Barracks 1 Jefferson Barracks Drive St. Louis, MO 63125 The following narrative is intended to provide an overview of the scope of work for the proposed project.
Period of Performance
222 calendar days after Notice to Proceed (NTP)
Scope of Work
Furnish complete construction services to replace all designated Building 51 roofs, including projections, entrance roofs, and connecting portions. The preliminary net roof area is approximately 56,000 square feet, subject to field verification. Provide a watertight thermoplastic polyolefin (TPO) roofing system in accordance with the VA-prepared drawings and specifications. Contractor shall submit shop drawings, product data, and installation details for all proposed materials, equipment, and systems to be installed or replaced under this contract for VA review prior to commencing the associated work. Submittals shall include applicable manufacturer's specifications and required engineering certifications.
Schedule, phasing, and occupied operations: Complete construction and closeout within 222 calendar days after the Notice to Proceed issue date. Building 51 remains occupied and operational 24 hours per day, seven days per week. Work hours are from 7:00 a.m. to 4:30 p.m., local time. Submit a contractor-developed phasing plan for the Contracting Officer's Representative (COR) to review before roofing. Complete both highest penthouse roof platforms first on the original building and the highest roof section first on the addition; either building portion may be started first. Maintain safe access, utilities, and required infection-control and HVAC-intake protection. Provide construction fall protection and keep the building watertight; coordinate service interruptions with the VA.

Investigation and Roofing Requirements:
Hazardous Materials: While neither Asbestos Containing Material nor Lead is expected to be encountered within the scope of this project, it will be the responsibility of the contractor to hire an independent 3rd party VPIH to complete the related work if they are to encounter a material that they deem suspicious.   

Demolition limit: At the original building (Zones 1-7, 13, and 14), remove the existing roofing assembly through the base sheet to the top of the Zonolite lightweight-concrete topping; retain the topping and underlying structural concrete deck. At the addition (Zones 8-12 and 15), remove the existing roofing assembly, including insulation and intervening layers, to the top of the metal roof deck; retain the deck and supporting structure. Clean and inspect retained surfaces, and repair deterioration within specified repair limits. Report differing construction or deterioration beyond those limits to the COR before proceeding with affected work.

New roof and mechanical securement: Install mechanically fastened rigid insulation, adhered cover board, and fully adhered 70-mil TPO roofing membrane with continuous hot-air-welded seams. Contractor shall verify that the proposed fastening system is compatible with Building 51's existing roof construction.

Parapets, penetrations, and retained metal: Extend new roofing up parapets to the existing flashing. Flash and seal, with the correct system specific boots, all roof penetrations with compatible membrane extending at least 8 inches above the finished roof, or higher where required by applicable VA criteria and manufacturer/warranty requirements. Retain metal flashings, flanges, and coping unless scheduled for replacement, and replace roofing beneath retained metal.

Specific Replacement and Repairs: 
Associated roof work: Retain rooftop HVAC units in place and replace roofing beneath elevated units and frames and around curbs. Replace old or deteriorated wooden rooftop support blocks with load-rated black rubber blocks compatible with the roofing; retain serviceable recently replaced blocks. Replace roof-drain covers/strainers and recondition retained drains with watertight connections. Reflash existing scuppers and provide new scuppers only where detailed; retain gutters and downspouts unless otherwise indicated. Correct approximately 250 square feet of depressed roof on the original building's middle section north of the penthouse to provide positive drainage. Replace expansion-joint weatherproofing/cover material at two original-building sections, approximately 40 linear feet each. Temporarily remove and reinstall the existing lightning-protection system in its original locations and configuration with new clips securing it; complete specified testing and certification. Repair approximately 150 linear feet of the existing movable stanchion-and-rope warning-line barrier. Replace the penthouse roof-access ladder to meet applicable VA safety requirements and OSHA criteria. Install 3-foot by 3-foot walking pads with 8-inch clear gaps along approximately 600 linear feet of total walkway route, including gaps. Provide positive drainage to roof drains and scuppers throughout all reroofed areas. Standing water shall not remain more than 48 hours after rainfall ends under conditions conducive to drying. Correct low spots and other drainage deficiencies that prevent compliance before final acceptance.

Skylights: Replace four skylights: two approximately 85 square feet each and two approximately 40 square feet each. Field-verify openings and provide complete watertight installations. Before fabrication, submit contractor shop drawings and supporting structural calculations signed and sealed by a licensed structural engineer responsible for their design/review.

Submittals, record drawings, and closeout: Provide required construction submittals and complete specified testing, inspections, and closeout. Submit a clean, coordinated as-built record drawing set in searchable PDF and editable CAD showing actual installed conditions and accepted changes; redline markups alone are not acceptable. Provide a 20-year no-dollar-limit (NDL) warranty and maintenance information, complete cleanup and restoration, and comply with contract records-management, privacy, and security requirements.

The estimated project cost range to complete this work is Between $2,000,000 and $5,000,000.
Pursuant to 38 USC 8127(d) and in accordance with Public Law 109-461, the Veterans Benefits, Health Care and Information Technology Act of 2006, this construction project will be solicited as a Total set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). 
The North American Industry Classification Code (NAICS) for this procurement is 235220 Commercial and Institutional Building Construction, with a small business size standard of $45.0 million. 
Contract Type: Firm Fixed. The duration of the project is estimated to be 210 calendar days from Notice to Proceed. This completion period includes final inspection and cleanup of the premises. 
Award will be made utilizing Highest technically rated with a fair and reasonable price approach in accordance with Federal Acquisition Regulation Part 15. 
Proposal submission instructions will be included in the solicitation package. 
The government plans to award without discussions. 
The offeror is responsible to monitor and download any amendments from the Contract Opportunities (https:// sam.gov) website, which may be issued to this solicitation.
In accordance with FAR 52.204-7, Required SAM, and in accordance with Veterans Affairs Acquisition Regulation (VAAR) 802.101, prospective contractors must be registered in SAM and in the Veteran Small Business Certification (sba.gov) databases under the applicable NAICS. 
Firms may obtain SAM information at http://www.sam.gov and Veteran Small Business Certification (sba.gov) information at https://veterans.certify.sba.gov
The solicitation package with project specifications and drawings should be available for download on or about December 7, 2026 and the proposal due date will be on or about January 15, 2027. An organized site visit will be scheduled and specific date and time will be made available at time of solicitation issuance. Only one site visit will be scheduled and interested offerors are highly encouraged to attend. No hard copies of the solicitation or drawings will be provided; and telephone requests or questions will NOT be accepted.
Please email requests or questions to Jennifer.Hill@va.gov and ensure that the subject line reads "FCA Replace Building 51 Roof, Project Number 657-27-103JB;  Solicitation Number: 36C25527R0020.

[View original listing](https://sam.gov/opp/d4533313366d49a8826392a623a45e36/view)