# SAM #N4008527R9006

Replace and integrate engine controls on three Camp Lejeune emergency generators

**Buyer:** Naval Facilities Engineering Systems Command Mid-Atlantic
**Posted:** November 13, 2026
**Respond By:** December 04, 2026
**Identifier:** N4008527R9006
**NAICS:** 236220, 238210, 238290

NAVFAC is soliciting construction services to replace and integrate engine controls on three emergency generators at Naval Medical Center Camp Lejeune.
- **Government buyer:** U.S. Department of the Navy, NAVFAC Mid-Atlantic / NAVFACSYSCOM Mid-Atlantic, ROICC Camp Lejeune. The equipment is at Naval Medical Center Camp Lejeune (NMCCL), part of the Defense Health Agency.
- **Scope:** Replace engine control units and associated controls on three 910 kW, 480/277 V generators with MTU/Detroit Diesel R1637M36 engines. The requested ECU model is **5275307654**; provide three **Marathon DVR 2400** voltage regulators.
- **Named OEMs and vendors:** **MTU / Detroit Diesel** engines, **Marathon** voltage regulators, and **Siemens** field service. The work also requires direct coordination with **RussElectric/Siemens** for factory-certified switchgear integration. Custom OEM upfit kits are configured for each engine serial number.
- **Testing and deliverables:** Provide temporary load banks and feeder cables; complete controls and switchgear integration, programming, testing, NFPA 110 commissioning, staff training, and updated manuals and as-built wiring diagrams. Use OEM-certified technicians and provide a factory-certified engineer for switchgear work.
- **Operational requirements:** Upgrade generators 1 and 3 before generator 2 to preserve generator availability. The installation and closeout period is 60 days after all materials are received and jointly inventoried on site; the procurement phase is outside that period.
- **Construction/site requirements:** Project work is phased. Coordinate utility interruptions in advance, use a professional utility locator, and follow site safety, security, access, and UXO-awareness requirements. A qualified superintendent and construction scheduling are required.

### Description

<p>Only M&amp;R MACC Contractors listed on the General Requirements cover page may submit a proposal for this ROICC Camp Lejeune area of responsibility project.&nbsp; See attached documents for scope of work and any applicable drawings.</p>

[View original listing](https://sam.gov/opp/eb04312d852e41579eca2dfdbd188e8a/view)