# SAM #15B61727Q00000002

FCC Lompoc Request for Nine 90-Minute Fire Escape Door Assemblies

**Buyer:** FCI Lompoc
**Posted:** November 05, 2026
**Respond By:** November 16, 2026
**Identifier:** 15B61727Q00000002
**NAICS:** 423390, 332321

The Federal Bureau of Prisons is seeking nine fire escape door assemblies for FCC Lompoc.
- **Government buyer:** U.S. Department of Justice, Federal Bureau of Prisons, FCC Lompoc.
- **Requested products:** Nine complete fire escape door assemblies: five right-hand outswing and four left-hand outswing. Each includes a 36-by-80-by-2-inch hollow-metal door, matching frame, and required hardware.
- **Construction and rating:** Minimum 12-gauge galvanneal steel; factory-primed for field painting; 90-minute fire rating compatible with the wall assembly. Assemblies must be positively pressure-tested and permanently labeled by an accepted third-party agency.
- **Hardware and preparation:** Three heavy-duty ball-bearing hinges, a self-latching panic/fire-exit device, lock set, adjustable surface-mounted closer, smoke and draft seals, and threshold if required. The frame must be prepared for an 80-series lock, keyed strike, pulls, and closer; hardware must meet applicable fire-rating and ANSI/BHMA Grade 1 requirements.
- **Compliance and submittals:** Provide product data, compliance confirmation, itemized pricing, and proposed manufacturing and delivery lead time. Requirements reference NFPA, UL, ANSI/BHMA, IBC, IFC, and OSHA; UL, Intertek/WH, and FM are cited as examples of testing or certification agencies.
- **OEMs and vendors:** No OEM, brand, or vendor is specified. Proposed alternatives must include supporting technical documentation, certifications, and test results.
- **Delivery:** FCC Lompoc, California.

### Description

<p><strong>&nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp; &nbsp;STATEMENT OF WORK / REQUEST FOR QUOTE<br />
A. INTRODUCTION:</strong></p>

<p><br />
1. The Federal Bureau of Prisons (FBOP), FCC Lompoc, 3901 Klein Blvd., Lompoc, CA 93436, is<br />
seeking quotes from qualified vendors for the supply and delivery of nine (9) complete fire<br />
escape door assemblies, including doors, frames, and all required hardware. The doors are for a<br />
prison facility application and must meet all relevant local, state, and federal fire and life safety<br />
codes.</p>

<p><br />
2. &quot;Equal or Better&quot; Product Substitution: Proposals must meet or exceed the specified product<br />
quality. If an alternative product or component is offered, the vendor must submit all technical<br />
documentation, certifications, and test results for consideration.</p>

<p><br />
3. Government&#39;s Right of Final Technical Acceptance: The government retains the sole and final<br />
authority to determine technical acceptance for all submitted products, based on the provided<br />
documentation and compliance with stated standards.</p>

<p><br />
<strong>B. SCOPE OF WORK:</strong></p>

<p><br />
1. The vendor shall provide all materials as specified below. All components must be new, U.L.<br />
Listed or labeled by a recognized testing agency acceptable to the Authority Having Jurisdiction<br />
(AHJ) and conform to the standards referenced herein.</p>

<p><br />
<strong>C. TECHNICAL SPECIFICATIONS:</strong></p>

<p><br />
<strong>TABLE 1: COMPONENTS</strong>: All units shall be identical unless otherwise noted.</p>

<ul>
	<li>Component
	<ul>
		<li>Requirement</li>
	</ul>
	</li>
	<li>Quantity
	<ul>
		<li>9 Complete Door Assemblies</li>
	</ul>
	</li>
	<li>Door Size
	<ul>
		<li>36&quot; wide x 80&quot; high x 2&quot; thick</li>
	</ul>
	</li>
	<li>Door Material
	<ul>
		<li>Hollow Metal Door, minimum 12 Gauge galvanneal steel</li>
	</ul>
	</li>
	<li>Core
	<ul>
		<li>Ribbed and Insulated (mineral core for fire rating is acceptable/preferred)</li>
	</ul>
	</li>
	<li>Fire Rating
	<ul>
		<li>Rating must be compatible with the wall&#39;s fire resistance rating, typically 75% of the wall&#39;s rating. See required fire rating for correctional facilities on Table 2</li>
	</ul>
	</li>
	<li>Handing
	<ul>
		<li>4 Left Hand Outswing, 5 Right Hand Outswing.</li>
	</ul>
	</li>
	<li>Frame Material
	<ul>
		<li>Minimum 12 Gauge galvanneal steel, fire-rated and labeled</li>
	</ul>
	</li>
	<li>Frame Type
	<ul>
		<li>Knock-down (KD) for drywall/unit masonry or welded for masonry. Frames are</li>
	</ul>
	</li>
</ul>

<p>to be prepared for 80 series lock, keyed 2 sides strike, surface pull on both<br />
sides and prepped for PA closer.</p>

<ul>
	<li>Finish
	<ul>
		<li>Factory primed for field painting</li>
	</ul>
	</li>
</ul>

<p><br />
<strong>TABLE 2: FIRE RATING:</strong></p>

<p><br />
The complete door assembly (door, frame, and all hardware) shall be <strong>90 minutes fire rated</strong>. This rating<br />
must be compatible with the fire-resistance rating of the specific wall assembly in which the door will be<br />
installed, as dictated by the building&#39;s fire safety plan and local code requirements.<br />
Category Requirement Description Applicable Standards &amp;<br />
Agencies</p>

<ul>
	<li>Listing &amp; Labeling
	<ul>
		<li>All components must be listed and labeled by a recognized third-party testing agency acceptable to the Authority Having Jurisdiction (AHJ).</li>
		<li>Underwriters Laboratories (UL), Intertek (WH), Factory Mutual (FM)</li>
	</ul>
	</li>
	<li>Testing Standard
	<ul>
		<li>Assemblies shall be tested under positive pressure conditions.</li>
	</ul>
	</li>
</ul>

<p>NFPA 252, ANSI/UL 10C</p>

<ul>
	<li>Labeling Visibility
	<ul>
		<li>A permanent, legible fire rating label must be affixed to both the door and the frame and remain visible after installation for inspection purposes.</li>
		<li>N/A</li>
	</ul>
	</li>
	<li>Code Compliance
	<ul>
		<li>Vendor must confirm that all components, when installed as an assembly, comply with relevant building and safety codes for correctional facilities (Group I-3 Occupancies, IBC).</li>
		<li>NFPA 80 (Standard for Fire Doors and Other Opening Protectives)</li>
		<li>International Building Code (IBC)</li>
	</ul>
	</li>
</ul>

<p><br />
<strong>TABLE 3: HARDWARE SPECIFICATIONS:</strong></p>

<p><br />
All hardware must be &quot;listed&quot; or &quot;labeled&quot; for use on a fire-rated assembly, compatible with the specified fire rating, and factory-prepped for ANSI/BHMA Grade 1 standards.</p>

<p><br />
Item Requirement Quantity<br />
per Door<br />
Notes</p>

<ul>
	<li>Hinges
	<ul>
		<li>Heavy-duty steel ball bearing hinges, UL Listed</li>
		<li>3</li>
	</ul>
	</li>
	<li>Exit Device
	<ul>
		<li>Panic Hardware/Fire Exit Hardware (rim or mortise type) self-latching</li>
		<li>1 set</li>
		<li>Must be a crossbar or touch bar device, operable with an applied force of 15 lbs or less.</li>
	</ul>
	</li>
	<li>Locking
	<ul>
		<li>Must be openable from the egress side at all times without special knowledge or tools. Keyed access from the exterior is permitted.</li>
		<li>1 set</li>
		<li>80 series lock, keyed 2 sides strike, surface pull on both sides and prepped for PA closer.</li>
	</ul>
	</li>
	<li>Door Closer
	<ul>
		<li>Heavy-duty, adjustable, surface-mounted, UL Listed</li>
		<li>1 unit</li>
		<li>Must be self-closing and ensure positive latching.</li>
	</ul>
	</li>
	<li>Seals
	<ul>
		<li>Smoke and draft control gasketing/seals</li>
		<li>1 set</li>
		<li>Required for a complete smoke-rated assembly.</li>
	</ul>
	</li>
	<li>Threshold
	<ul>
		<li>[Specify if required, e.g., 1/2&quot; beveled aluminum, non-combustible]</li>
		<li>1 unit (if required)</li>
	</ul>
	</li>
</ul>

<p><br />
<strong>D. CODE AND STANDARD REQUIREMENTS:</strong></p>

<p><br />
1. All supplied materials and the complete assembly must comply with the latest editions of the<br />
following codes and standards (or local equivalents as adopted by the AHJ):</p>

<ul>
	<li>NFPA 80: Standard for Fire Doors and Other Opening Protectives</li>
	<li>NFPA 101: Life Safety Code</li>
	<li>International Building Code (IBC)</li>
	<li>International Fire Code (IFC)</li>
	<li>OSHA requirements for exit routes</li>
	<li>UL 10C or NFPA 252: Standard for positive pressure fire testing of door assemblies</li>
	<li>UL 1784: Standard for Air Leakage Tests of Door Assemblies (if smoke rating is required)</li>
</ul>

<p><br />
2. Vendors must confirm that all components, when installed as an assembly, will bear a permanent,<br />
legible label from a recognized third-party testing agency (e.g., UL, Intertek/WH, FM).</p>

<p><br />
<strong>E. SUBMISSION REQUIREMENTS:</strong></p>

<p><br />
1. Itemized pricing for doors, frames, hardware, and any included accessories.<br />
2. Proposed lead time for manufacturing and delivery to FCC Lompoc<br />
3. Confirmation of compliance with all referenced codes and standards.<br />
4. Cut sheets/product data for all proposed items.</p>

<p><br />
<strong>F. DELIVERY OF MATERIALS:</strong></p>

<p><br />
1. Deliveries shipped directly to FCC LOMPOC can only be received between 7:30 a.m. and 2:00<br />
p.m., Monday through Friday, excluding Federal Holidays.</p>

<p><br />
2. POC: Mr. Fernando Pena, BOP Engineering Technician, FXPena@bop.gov, or 805-735-2771</p>

<p><br />
3. FBOP will be responsible for receiving or signing deliveries.</p>

<p><br />
4. FCC LOMPOC will provide resources for loading and unloading materials or equipment upon<br />
arrival.</p>

[View original listing](https://sam.gov/opp/889b960037f64c288fd031fb8d5c49e3/view)