Award
Los Angeles General Medical Center PDPP-HG-27005309
COOLING TOWER MECHANICAL REPLACEMENT Lock out and tag out the unit, to de-energize the fan motor. Disconnect and remo...
Recipient
EFFICIENT AIRE MECHANICAL, INC
Award Amount
$24,896.38
Ceiling
$24,896.38
Awarded
November 03, 2026
Identifier
PDPP-HG-27005309
Description
COOLING TOWER MECHANICAL REPLACEMENT Lock out and tag out the unit, to de-energize the fan motor. Disconnect and remove the existing Geareducer, motor and coupling from the fan deck. Transport all equipment to and from the roof safely Furnish and install one (1) new Marley Geareducer assembly. Furnish and install one (1) new 10 HP premium-efficiency electric motor Furnish and install one (1) new Marley coupling assembly with new coupling element. Furnish and install new stainless hold-down hardware, shim set and Geareducer spirol pins. Provide and fill the Geareducer with synthetic ISO 150 gear oil and verify the operating level. Laser-align the motor and Geareducer following installation. Dispose of old equipment and all job related debris from site Run and verify at completion rotation, vibration and amp draw checked against nameplate. JOB SITE: ROYBAL COMPREHENSIVE CENTER 245 S FETTERLY AVE LOS ANGELES, CA 90022-1605; LABOR FOR MECHANICAL REPLACEMENT ALL PRICING IN ACCORDANCE WITH QUOTE # 2213A DATED : 09-28-26 ******************************************************* INTERNAL USE ONLY KAREN DALE kdale@dhs.lacounty.gov REQ : 1019-27039 O2718644 UNIT : 84618 REQUESTOR : WAYNE NIEMAND EMAIL : wniemand@dhs.lacounty.gov EMAIL INVOICES TO : GHXODAP.Lacounty@firstsource.com